OSHA AI Agent
Get instant answers to any safety question.
Request Demo
OSHA 1910.164

Fire detection system requirements

Subpart L

22 Questions & Answers
10 Interpretations

Questions & Answers

Under 1910.164(a), which automatic fire detection systems does this standard apply to?

This standard applies to all automatic fire detection systems that are installed to meet the requirements of a specific OSHA standard. See Scope and application in 1910.164(a).

Under 1910.164(b)(1), what does "approved for the purpose for which they are intended" mean for fire detection devices and equipment?

Under 1910.164(b)(1), employers must ensure detection devices and equipment are suitable and approved for the tasks they will perform — in other words, each device must be appropriate for the environment and function it will serve. See Installation and restoration; 1910.164(b)(1).

  • Practical steps: choose devices listed by a recognized testing laboratory or recommended by the manufacturer for that application, and document why the device is appropriate.

Under 1910.164(b)(2), how quickly must employers restore fire detection systems after a test or alarm?

Under 1910.164(b)(2), employers must restore all fire detection systems and components to normal operating condition as promptly as possible after each test or alarm. See 1910.164(b)(2).

  • Practical steps: keep spare parts on site or available locally, have written procedures for rapid repair, and assign responsibility so restoration is not delayed.

Under 1910.164(b)(2), do employers need spare detection devices or components that are normally destroyed when detecting fires?

Yes. Under 1910.164(b)(2), employers must have spare detection devices and components that are normally destroyed in the detection process available on the premises or from a local supplier in sufficient quantities and locations for prompt restoration of the system. See 1910.164(b)(2).

  • Practical guidance: perform an inventory of device types that are one-time-use (e.g., fusible links, some thermal elements), estimate how many spares are reasonable based on system size and critical areas, and document procurement sources and lead times.

Under 1910.164(c)(1), can fire detection systems be left inoperable during repairs or maintenance?

Under 1910.164(c)(1), employers must maintain all systems in an operable condition except during repairs or maintenance. See Maintenance and testing; 1910.164(c)(1).

  • Practical steps: schedule repairs to minimize downtime, use temporary measures (e.g., guarded, alternate detectors) when feasible, and document out-of-service periods and planned restoration times.

Under 1910.164(c)(2), how often must fire detectors and detection systems be tested and adjusted?

Under 1910.164(c)(2), employers must test and adjust fire detectors and detection systems as often as needed to maintain proper reliability and operating condition, except that factory-calibrated detectors need not be adjusted after installation. See 1910.164(c)(2).

  • Practical guidance: create a testing schedule based on device type, environmental conditions, and manufacturer guidance; more frequent testing is needed in dirty or harsh environments.

Under 1910.164(c)(3), what is required for pneumatic and hydraulic operated detection systems installed after January 1, 1981?

Under 1910.164(c)(3), pneumatic and hydraulic operated detection systems installed after January 1, 1981, must be equipped with supervised systems. See 1910.164(c)(3).

  • Practical explanation: "supervised" means the system monitors its own integrity (for example, sensing line breaks, pressure loss, or other failures) and alerts when the detection system cannot function properly; follow manufacturer and industry practice for supervising such systems.

Under 1910.164(c)(4), who may perform servicing, maintenance, and testing of fire detection systems?

Under 1910.164(c)(4), servicing, maintenance, and testing (including cleaning and sensitivity adjustments) must be performed by a trained person knowledgeable in the operations and functions of the system. See 1910.164(c)(4).

  • Practical steps: document training records, ensure technicians know system functions and manufacturer procedures, and maintain competency through refresher training and supervised practice.

Under 1910.164(c)(5), how often must detectors that collect dirt, dust, or particulates be cleaned?

Under 1910.164(c)(5), detectors that need cleaning of dirt, dust, or other particulates to be fully operational must be cleaned at regular periodic intervals. See 1910.164(c)(5).

  • Practical guidance: set cleaning intervals based on the environment (e.g., monthly in dusty workshops, quarterly in cleaner spaces), follow manufacturer cleaning methods, and document cleaning dates and observations.

Under 1910.164(d)(1), how should detection equipment installed outdoors or in corrosive atmospheres be protected?

Under 1910.164(d)(1), employers must protect detection equipment installed outdoors or in corrosive atmospheres from corrosion, for example by providing a canopy, hood, or other suitable weather protection. See Protection of fire detectors; 1910.164(d)(1).

  • Practical measures: use corrosion-resistant materials, provide enclosures rated for the environment, and inspect coatings and seals regularly.

Under 1910.164(d)(2), how must detection equipment be protected from mechanical or physical impact?

Under 1910.164(d)(2), employers must locate or otherwise protect detection equipment so it is protected from mechanical or physical impact that might render it inoperable. See 1910.164(d)(2).

  • Practical steps: mount detectors out of high-traffic impact zones, use guards or cages where necessary, and mark or restrict access to areas with sensitive detectors.

Under 1910.164(d)(3), how must detectors be supported relative to their wiring or tubing?

Under 1910.164(d)(3), detectors must be supported independently of their attachment to wires or tubing. See 1910.164(d)(3).

  • Practical explanation: use proper mechanical supports (brackets, mounts) so the detector weight or movement is not borne by signal wires or sensing tubes, which could cause failure or false alarms.

Under 1910.164(e)(1), what is required for detection systems that actuate fire extinguishment or suppression systems?

Under 1910.164(e)(1), detection systems that actuate fire extinguishment or suppression systems must be designed to operate in time to control or extinguish a fire. See Response time; 1910.164(e)(1).

  • Practical steps: ensure detector placement and sensitivity are coordinated with the suppression system design, test actuation times during commissioning, and document test results.

Under 1910.164(e)(2), how should detection systems for employee alarm and evacuation be designed?

Under 1910.164(e)(2), detection systems intended to trigger employee alarm and evacuation must be designed and installed to provide a warning that allows emergency action and safe escape of employees. See 1910.164(e)(2).

  • Practical guidance: ensure alarms are audible/visible throughout occupied areas, maintain backup power, and regularly test notification coverage and audibility.

Under 1910.164(e)(3), can an employer delay an alarm initiated by fire detector actuation?

Under 1910.164(e)(3), an employer may not delay alarms or devices initiated by detector actuation for more than 30 seconds unless the delay is necessary for the immediate safety of employees, and any such delay must be addressed in an emergency action plan that meets 1910.38. See 1910.164(e)(3) and the Emergency action plans in 1910.38.

  • Practical steps: avoid unnecessary verification delays; if a delay beyond 30 seconds is needed for safety (for example, to prevent panic during hazardous operations), document and justify it in the employer's emergency action plan.

Under 1910.164(f), how should employers determine the number, location, and spacing of detecting devices?

Under 1910.164(f), employers must base the number, spacing, and location of fire detectors on design data obtained from field experience or tests, engineering surveys, the manufacturer's recommendations, or a recognized testing laboratory listing. See Number, location and spacing of detecting devices; 1910.164(f).

  • Practical steps: use manufacturer guidance, documented engineering surveys, and listed layouts from testing labs; update placement after changes to operations or the building layout.

Under 1910.164(c)(2), do factory-calibrated detectors ever require adjustment after installation?

Under 1910.164(c)(2), factory-calibrated detectors need not be adjusted after installation. See 1910.164(c)(2).

  • Practical note: even if adjustment isn't required, factory-calibrated detectors still require routine inspection, testing, and cleaning as specified in other parts of 1910.164.

Under 1910.164(b) and (c), what records or documentation should employers keep to show compliance with installation, restoration, maintenance, and testing?

While 1910.164 does not specify detailed recordkeeping requirements, employers should document installation approvals, restoration actions, test schedules and results, maintenance performed, cleaning intervals, and training of personnel to demonstrate compliance with 1910.164(b) and 1910.164(c).

  • Practical list: keep device approval/listing documentation, spare parts inventory, test logs with dates and outcomes, maintenance and cleaning logs, and records of technician training and qualifications.

Under 1910.164(c)(4), what should "a trained person knowledgeable in the operations and functions of the system" know before servicing fire detection systems?

Under 1910.164(c)(4), the trained person should understand the system's operation, sensitivity settings, cleaning requirements, testing procedures, and manufacturer instructions so they can perform servicing, maintenance, and testing correctly. See 1910.164(c)(4).

  • Practical elements: training on system schematics, alarm logic, supervised-line diagnostics, safe isolation for maintenance, and how to restore systems promptly after a test or alarm.

Under 1910.164(b)(2) and (f), how should an employer plan spares and system design to minimize downtime after a detector activation that destroys parts of the system?

Under 1910.164(b)(2) and (f), employers should keep on-site or locally available spare parts for detectors normally destroyed by fire detection, and design detector layouts based on recognized data so systems can be restored promptly and reliably. See 1910.164(b)(2) and 1910.164(f).

  • Practical steps: perform a risk-based spare parts analysis, store critical spares near protected areas, and use modular designs to allow quick replacement.

Under 1910.164(e)(3) and 1910.38, what must be included in the emergency action plan if alarms are delayed for safety reasons?

Under 1910.164(e)(3) and 1910.38, any delay in alarms beyond 30 seconds for immediate employee safety must be addressed in the employer's emergency action plan, which must meet the requirements of 1910.38 and explain when and why the delay is necessary and how employee safety is protected. See 1910.164(e)(3).

  • Practical items to include: justification for the delay, procedures to protect employees during the delay, notification protocols, and training so employees understand the special procedure.

Under 1910.164(d), can detection equipment be mounted directly on signal wires or tubing without separate supports?

No. Under 1910.164(d)(3), detectors must be supported independently of their attachment to wires or tubing, so they cannot rely on those connections as their sole support. See 1910.164(d)(3).

  • Practical action: install proper brackets or mounting hardware so the detector's weight and any forces are carried by mechanical supports rather than cabling or tubing.