AC systems rated 50 to 1000 volts must be grounded when any of these conditions apply: the system can be grounded so the maximum voltage to ground on ungrounded conductors does not exceed 150 volts; the system is a nominal three-phase, four-wire wye where the neutral is a circuit conductor; the system is a nominal three-phase, four-wire delta where a phase midpoint is used as a circuit conductor; or a service conductor is uninsulated. See 1910.304(g)(1)(iv).
Common exceptions where grounding is not required include (but are not limited to): systems used exclusively to supply industrial electric furnaces, separately derived systems used exclusively for rectifiers supplying adjustable speed industrial drives, certain separately derived control systems under strict conditions, isolated power systems in health care facilities, and high-impedance grounded neutral systems meeting specific safeguards. See 1910.304(g)(1)(v).
- When you claim an exception (for example, for control circuits), ensure conditions such as qualified-person servicing, ground detectors, and continuity-of-power requirements in the standard are met.
(Authority: 1910.304(g)(1)(iv)–(v)).