OSHA AI Agent
Get instant answers to any safety question.
Request Demo
OSHA 1926.405

Wiring methods and requirements

Subpart K

41 Questions & Answers
10 Interpretations

Questions & Answers

Under 1926.405(a), do the wiring method rules apply to conductors that are an integral part of equipment (like motors or controllers)?

No — the wiring method rules in 1926.405(a) do not apply to conductors that form an integral part of equipment such as motors, controllers, motor control centers, and similar equipment. Employers should treat those conductors as part of the equipment rather than as separate wiring under 1926.405(a).

Under 1926.405(a)(1)(i), what is required for electrical continuity of metal raceways and enclosures?

Metal raceways, cable armor, and other metal enclosures must be metallically joined into a continuous conductor and be connected to boxes, fittings, and cabinets to provide effective electrical continuity. This means all metal parts that serve as raceway or enclosure must be bonded so they form a continuous grounding/return path as required by 1926.405(a)(1)(i).

Under 1926.405(a)(1)(ii), can wiring be installed inside ducts used to transport dust, loose stock, or flammable vapors?

No — no wiring systems of any type may be installed in ducts used to transport dust, loose stock, flammable vapors, or in ducts used for vapor removal or in shafts containing only such ducts. Installing wiring in those ducts is prohibited by 1926.405(a)(1)(ii).

Under 1926.405(a)(2)(i), what is the scope and duration requirement for temporary wiring on a construction site?

Temporary wiring must comply with the temporary-wiring provisions and be removed immediately when construction or the purpose for which it was installed is complete. Paragraph 1926.405(a)(2)(i) states that temporary power and lighting may be of a class less than permanent installations but otherwise must meet the subpart's permanent-wiring requirements unless specifically modified, and temporary wiring shall be removed immediately upon completion.

Under 1926.405(a)(2)(ii)(A), where must temporary feeders originate and how may they be routed?

Temporary feeders must originate in a distribution center and may be run as multiconductor cord or cable assemblies, within raceways, or as open conductors on insulators (not more than 10 feet apart) where they are not subject to physical damage. These routing and origin requirements are in 1926.405(a)(2)(ii)(A).

Under 1926.405(a)(2)(ii)(B), where must temporary branch circuits originate and how must they be protected?

Temporary branch circuits must originate in a power outlet or panelboard and may be run as multiconductor cord/cable assemblies, open conductors, or in raceways, and all conductors must be protected by overcurrent devices sized to their ampacity. See 1926.405(a)(2)(ii)(B).

Under 1926.405(a)(2)(ii), where may runs of open conductors be located and how often must they be fastened?

Runs of open conductors must be located where they will not be subject to physical damage and must be fastened at intervals not exceeding 10 feet (3.05 m). Also, branch-circuit conductors must not be laid on the floor. These rules are in 1926.405(a)(2)(ii).

Under 1926.405(a)(2)(ii)(C), when must temporary branch circuits include a grounding conductor and what type of receptacles are required?

Temporary branch circuits that supply receptacles or fixed equipment must contain a separate equipment grounding conductor if run as open conductors, and all receptacles must be of the grounding type and electrically connected to the grounding conductor unless the branch circuit is installed in a complete metallic raceway. Also, receptacles for non-lighting uses shall not be on branch circuits supplying temporary lighting. See 1926.405(a)(2)(ii)(C).

Under 1926.405(a)(2)(ii)(D), what disconnecting means are required for temporary circuits?

Temporary circuits must have disconnecting switches or plug connectors installed so that all ungrounded conductors of each temporary circuit can be disconnected. This requirement is stated in 1926.405(a)(2)(ii)(D).

Under 1926.405(a)(2)(ii)(E), how must lamps for general illumination in temporary wiring be protected and grounded?

All lamps used for general illumination must be protected from accidental contact or breakage, and metal-case sockets must be grounded. These protections are required by 1926.405(a)(2)(ii)(E).

Under 1926.405(a)(2)(ii)(F), may temporary lights be suspended by their electric cords?

No — temporary lights must not be suspended by their electric cords unless both the cords and lights are specifically designed for suspension by the cord. This prohibition is found in 1926.405(a)(2)(ii)(F).

Under 1926.405(a)(2)(ii)(G), what voltage is allowed for portable electric lighting used in wet or conductive locations?

Portable electric lighting used in wet or other conductive locations must operate at 12 volts or less, but 120-volt lights may be used only if protected by a ground-fault circuit interrupter (GFCI). See 1926.405(a)(2)(ii)(G).

Under 1926.405(a)(2)(ii)(H), when must a box be used with metal-clad or metal-sheathed cable systems?

A box must be used wherever a change is made to a raceway system or a cable system that is metal-clad or metal-sheathed. This requirement is in 1926.405(a)(2)(ii)(H).

Under 1926.405(a)(2)(ii)(I), how should flexible cords and cables be protected when passing through doorways or pinch points?

Flexible cords and cables must be protected from damage; sharp corners and projections must be avoided, and cords may pass through doorways or similar openings only if protection is provided to prevent damage. See 1926.405(a)(2)(ii)(I).

Under 1926.405(a)(2)(ii)(J), what type of extension cord sets and flexible cords are required for portable tools and temporary lights?

Extension cord sets used with portable electric tools and appliances must be three‑wire type and designed for hard or extra‑hard usage; flexible cords for temporary and portable lights must also be designed for hard or extra‑hard usage. See 1926.405(a)(2)(ii)(J).

Under 1926.405(a)(2)(iii), what guarding is required for temporary wiring over 600 volts nominal?

For temporary wiring over 600 volts nominal, employers must provide fencing, barriers, or other effective means to prevent access by anyone other than authorized and qualified personnel. See 1926.405(a)(2)(iii).

Under 1926.405(b)(1), how must conductors entering boxes, cabinets, or fittings be protected?

Conductors entering boxes, cabinets, or fittings must be protected from abrasion, and openings through which conductors enter must be effectively closed; unused openings must also be effectively closed. This protection requirement is in 1926.405(b)(1).

Under 1926.405(b)(2), what are the cover and canopy requirements for pull boxes, junction boxes, and outlet boxes?

All pull boxes, junction boxes, and fittings must have covers; if metal covers are used they must be grounded. In energized installations each outlet box must have a cover, faceplate, or fixture canopy, and covers with holes for flexible cord pendants must have bushings or smooth, well-rounded surfaces for the cords. See 1926.405(b)(2).

Under 1926.405(b)(3)(i) and (ii), what special requirements apply to pull and junction boxes for systems over 600 volts nominal?

Pull and junction boxes for systems over 600 volts must provide a complete enclosure for the conductors and be closed by securely fastened covers; covers must be permanently marked "HIGH VOLTAGE" on the outside and be readily visible and legible. See 1926.405(b)(3)(i) and 1926.405(b)(3)(ii).

Under 1926.405(c) and (d), what are the basic installation rules for knife switches, switchboards, and panelboards?

Knife switches must be connected so blades are dead when the switch is open and be located so gravity will not tend to close them; switchboards with exposed live parts must be in permanently dry locations and accessible only to qualified persons, and panelboards must be mounted in cabinets, cutout boxes, or enclosures and be dead front unless accessible only to qualified persons. See 1926.405(c) and 1926.405(d).

Under 1926.405(e)(1) and (e)(2), what are the enclosure requirements for damp or wet locations?

Enclosures (cabinets, boxes, fittings, panelboard enclosures) in damp or wet locations must be installed to prevent moisture or water from entering and accumulating; in wet locations enclosures must be weatherproof, and switches and circuit breakers in wet locations must be enclosed in weatherproof enclosures. See 1926.405(e)(1) and 1926.405(e)(2).

Under 1926.405(f), what are the basic requirements for conductors used in general wiring?

All conductors for general wiring must be insulated (unless otherwise permitted) with insulation suitable for the voltage, operating temperature, and location, and insulated conductors must be distinguishable by color or other means to identify grounded, ungrounded, or equipment grounding conductors. See 1926.405(f).

Under 1926.405(g)(1)(i), what are the permitted uses of flexible cords and cables?

Flexible cords and cables are permitted only for specific uses such as pendants, wiring of fixtures, connection of portable lamps or appliances, elevator cables, wiring of cranes and hoists, connection of stationary equipment to permit frequent interchange, preventing transmission of noise or vibration, and appliances designed for removal for maintenance and repair. These permitted uses are listed in 1926.405(g)(1)(i).

Under 1926.405(g)(1)(ii) and (g)(1)(iii), when must flexible cords have attachment plugs and what are prohibited uses of flexible cords?

If flexible cords are used for connection of portable lamps/appliances, connecting stationary equipment for interchange, or appliances designed for removal, they must be equipped with attachment plugs and energized from receptacle outlets per 1926.405(g)(1)(ii). Flexible cords are prohibited as a substitute for fixed wiring; where run through holes in walls, ceilings, or floors; where run through doorways/windows except as allowed by 1926.405(a)(2)(ii)(I); where attached to building surfaces; or where concealed behind building walls, ceilings, or floors, per 1926.405(g)(1)(iii).

Under 1926.405(g)(2)(ii) and (g)(2)(iii), what marking and splice rules apply to certain types of flexible cords?

Cords of type SJ, SJO, SJT, SJTO, S, SO, ST, and STO must be durably marked with the type designation, size, and number of conductors; flexible cords generally must be used in continuous lengths without splice or tap, though hard service flexible cords No. 12 or larger may be repaired with a splice that preserves the cord's insulation and outer-sheath properties. See 1926.405(g)(2)(ii) and 1926.405(g)(2)(iii).

Under 1926.405(g)(2)(iv) and (g)(2)(v), what are the requirements for strain relief and cords passing through holes?

Flexible cords must be connected to devices and fittings with strain relief to prevent pull from being transmitted to joints or terminal screws, and flexible cords passing through holes in covers, outlet boxes, or similar enclosures must be protected by bushings or fittings. See 1926.405(g)(2)(iv) and 1926.405(g)(2)(v).

Under 1926.405(h), what are the construction requirements for multiconductor portable cables used above 600 volts nominal?

Multiconductor portable cable supplying power to portable or mobile equipment over 600 volts nominal must use No. 8 or larger conductors with flexible stranding, and cables operated over 2000 volts must be shielded to confine voltage stresses to the insulation. See 1926.405(h).

Under 1926.405(i), where may fixture wires be used and when are they not permitted as branch-circuit conductors?

Fixture wires may be used only inside lighting fixtures (or similar enclosed equipment) and to connect fixtures to branch-circuit conductors, and they may not be used as branch-circuit conductors except for Class 1 power-limited circuits. See Uses permitted in 1926.405(i)(2) and Uses not permitted in 1926.405(i)(3).

  • Practical point: use fixture wire only where it will be enclosed or protected and not subject to bending or twisting, and do not run it as a general-purpose branch circuit conductor unless it is for a permitted Class 1 power-limited circuit.

Under 1926.405(i)(1), what must be true about fixture wire when it is used as a grounded conductor?

A fixture wire used as a grounded conductor must be suitable for the voltage, temperature, and location of use and must be identified as the grounded conductor. See the General requirements in 1926.405(i)(1).

  • Practical point: mark or color the conductor appropriately (for example, the standard grounded conductor identification) and ensure the wire type is rated for the fixture’s environment and temperature.

Under 1926.405(j)(1)(iii), what specific safety features are required for portable handlamps?

Portable handlamps must be wired with flexible cord and a polarized or grounding attachment plug, have an insulating handle, a substantial guard, and must not use metal-shell, paper-lined lampholders. See Portable lamp requirements in 1926.405(j)(1)(iii) and the related provisions 1926.405(j)(1)(iii)(A)–(D).

  • Practical checklist: flexible cord with correct plug type; molded or other insulating handle; guard attached to lampholder or handle; no metal shell paper-lined lampholders.

Under 1926.405(j)(1)(iii)(D), must metallic guards on portable handlamps be grounded?

Yes — metallic guards on handlamps must be grounded by an equipment grounding conductor run inside the power supply cord. See 1926.405(j)(1)(iii)(D).

  • Practical point: use a three-conductor cord with the grounding conductor connected to the guard and to the equipment grounding terminal of the plug so the guard is bonded to equipment ground.

Under 1926.405(j)(1)(ii) and 1926.405(j)(1)(iv), how must lighting fixtures and screw-shell lampholders be supported and protected in wet or damp locations?

Fixtures, lampholders, rosettes, and receptacles must be securely supported, and screw-shell lampholders used in wet or damp locations must be of the weatherproof type; fixtures installed in wet or damp locations must be identified for that use and installed so water cannot enter or accumulate in electrical parts. See Support and general requirements in 1926.405(j)(1)(ii), Lampholders in 1926.405(j)(1)(iv), and Fixtures in 1926.405(j)(1)(v).

  • Practical tips: don’t support heavy fixtures by a lampholder screw shell; select fixtures and lampholders listed for wet/damp locations; make sure housings and wireways shed water and remain dry.

Under 1926.405(j)(2), how must receptacles, cord connectors, and attachment plugs be configured and selected for different voltages and for wet/damp locations?

Receptacles, cord connectors, and plugs must be constructed so they won’t accept a plug rated for a different voltage or current than the device is intended for, and receptacles installed in wet or damp locations must be designed for that location. See Configuration rules in 1926.405(j)(2)(i) and Damp/wet location requirement in 1926.405(j)(2)(ii).

  • Practical point: use properly keyed or non-interchangeable plugs/receptacles for different voltages; in wet areas use weatherproof or gasketed devices and covers rated for the environment.

Under 1926.405(j)(4)(ii), what are the basic requirements for disconnecting means for motors and controllers?

The disconnecting means must disconnect the motor and controller from all ungrounded supply conductors, be designed so no pole can be operated independently, be located in sight from the controller (unless otherwise permitted with proper marking), plainly indicate ON/OFF position, and be readily accessible. See Disconnecting means requirements in 1926.405(j)(4)(ii).

  • Practical points: install disconnects that clearly show open/closed; place them within 50 feet and visible from the controller unless the exception for over-600 V controllers applies with marking and lockout provisions.

Under 1926.405(j)(4)(ii)(F), when may a single disconnecting means serve a group of motors?

A single disconnecting means may serve a group of motors if they drive parts of a single machine, are protected by one set of branch-circuit protective devices, or are in a single room in sight from the disconnect location. See Conditions in 1926.405(j)(4)(ii)(F)(1)–(3).

  • Practical example: multiple motors on one machine (e.g., a multi-spindle woodworking machine) can use one disconnect; separate independent motors in different areas generally need individual disconnects.

Under 1926.405(j)(4)(iii), what protection is required for motors and motor branch-circuit conductors against overloads, short-circuits, and ground faults?

Motors, motor-control apparatus, and motor branch-circuit conductors must be protected against overheating from overloads or failure to start, and against short-circuits and ground faults, except where overload protection would create a greater hazard (for example, fire pumps). See Motor protection requirements in 1926.405(j)(4)(iii).

  • Practical note: ensure proper overcurrent devices, overload relays, and ground-fault protection are installed unless a documented safety exception applies.

Under 1926.405(j)(4)(iv)(A), when may exposed live parts of motors and controllers be left unguarded, and what alternative guards are acceptable?

Exposed live parts of motors and controllers operating at 50 volts or more between terminals must be guarded against accidental contact unless they are placed where access is restricted to qualified persons (in a room or enclosure), elevated on a balcony or platform to exclude unqualified persons, or elevated 8 feet or more above the floor. See Guarding and permitted alternatives in 1926.405(j)(4)(iv)(A)(1)–(3).

  • Practical application: if regular attendance or adjustment is needed during operation and the only guard is location-based, provide insulating mats or platforms per 1926.405(j)(4)(iv)(B).

Under 1926.405(j)(5), what are key installation and safety requirements for transformers, especially those over 35 kV or oil-insulated units?

Transformers over 35 kV installed indoors must be placed in a vault, and oil-insulated transformers that present a fire hazard indoors must also be in a vault; operating voltages of exposed live parts must be visibly marked and transformer installations must be protected from fire hazards and unauthorized access. See Transformer rules in 1926.405(j)(5)(ii)–(iv).

  • Additional vault requirements: vaults must contain fire/combustible liquids, prevent unauthorized access, allow inside egress (locks openable from inside), exclude foreign pipes/ducts, and prohibit storage of materials in the vault (1926.405(j)(5)(vi)–(viii)).

  • Practical point: label voltage levels on equipment and keep combustible materials away from transformers.

Under 1926.405(j)(6), what safety features are required for capacitors and for capacitors rated over 600 volts?

All capacitors (except surge or component capacitors) must have an automatic means to drain stored charge and keep them discharged after disconnection; capacitors over 600 volts must have interlocked isolating or disconnecting switches or prominently displayed caution signs to prevent switching of load current. See Capacitor drainage in 1926.405(j)(6)(i) and Over-600 volt additional requirements in 1926.405(j)(6)(ii)(A).

  • Practical safety tip: include automatic bleeder devices or grounded discharge paths and lockout/tagout procedures where appropriate; add visible warnings on high-voltage capacitor installations.

Under 1926.405, are portable cables allowed to be operated with splices?

Portable cables must not be operated with splices unless the splices are permanent molded, vulcanized, or equivalent type. See the general provision in 1926.405 that requires portable cables to avoid non-permanent splices and to have strain relief at connections and terminations.

  • Practical note: if a field splice is necessary for a portable cable, use a listed permanent splice assembly and provide proper strain relief and locking connectors to prevent opening while energized.

Under 1926.405(j)(1)(iii) and 1926.405(j)(1)(iii)(B), what are the plug and wiring requirements for portable lamps and how must the grounded conductor be connected for Edison-based lampholders?

Portable lamps must be wired with flexible cord and an attachment plug that is polarized or of the grounding type; if the lamp uses an Edison-type lampholder, the grounded conductor must be identified and attached to the screw shell and the identified blade of the plug. See Portable lamp wiring in 1926.405(j)(1)(iii) and the specific requirement about grounded conductors for Edison lampholders in 1926.405(j)(1)(iii).

  • Practical tip: use three-conductor cords and a grounding-type plug when metal parts could become energized; clearly mark (or color) the grounded conductor to avoid miswiring.