Under 1926.960(a), to whom does the rule 'Working on or near exposed energized parts' apply?
This rule applies to any work on exposed live parts or near enough to them to expose an employee to hazards. See Application in 1926.960(a).
Subpart V
This rule applies to any work on exposed live parts or near enough to them to expose an employee to hazards. See Application in 1926.960(a).
Only qualified employees are allowed to work on or with exposed energized lines or parts and to work in areas with unguarded, uninsulated energized parts operating at 50 volts or more. See Qualified employees only in 1926.960(b)(1).
Electric lines and equipment must be considered and treated as energized unless they have been deenergized in accordance with 1926.961. See Treat as energized in 1926.960(b)(2).
At least two employees must be present for specified high-hazard work involving parts energized above 600 volts, including installation, removal, or repair of such lines or equipment, work with mechanical equipment near those parts, and other work with equivalent electrical hazards. See At least two employees listed in 1926.960(b)(3)(i).
The two-employee requirement does not apply to routine circuit switching where the employer can demonstrate safe conditions, to work done with live-line tools when the worker cannot reach or be exposed to energized parts, or to emergency repairs needed to protect the public. See Exceptions in 1926.960(b)(3)(ii).
Employers must establish minimum approach distances at least as large as those computed by Table V-2 for AC systems or Table V-7 for DC systems. See Minimum approach distances in 1926.960(c)(1)(i).
For voltages over 72.5 kV, the employer must determine the maximum anticipated per‑unit transient overvoltage, phase‑to‑ground, by engineering analysis or assume a value per Table V‑8 no later than April 1, 2015. See Transient overvoltage requirement in 1926.960(c)(1)(ii).
When portable protective gaps are used, the employer must size the maximum anticipated per‑unit transient overvoltage so there are five standard deviations between the gap's statistical sparkover voltage and the statistical withstand voltage used for the electrical component of the minimum approach distance, and must make any engineering analysis available upon request. See Transient overvoltage and analysis availability in 1926.960(c)(1)(ii).
An employee may approach closer than the minimum approach distance only if the employee is insulated from the energized part by rubber insulating gloves (with sleeves), the energized part is insulated from the employee and other conductive objects, or the employee is insulated from other conductive objects in accordance with live‑line barehand work requirements in 1926.964(c). See Conditions allowing closer approach in 1926.960(c)(1)(iii).
Rubber insulating sleeves are not required if exposed energized parts on which the employee is not working are insulated from the employee, and the insulation is installed from a position that does not expose the employee's upper arm to contact with other energized parts. See Exceptions in 1926.960(c)(2)(i)(A)–(B).
The employee must put on rubber insulating gloves and sleeves in a position where they cannot reach into the employer's established minimum approach distance and must not remove them until they are again in a position where they cannot reach into that minimum approach distance. See Donning and removing requirements in 1926.960(c)(2)(ii)(A)–(B).
The employer must ensure each employee, as worksite conditions allow, works from a position where a slip or shock will not bring the employee's body into contact with exposed, uninsulated parts energized at a different potential. See Working from below in 1926.960(d)(1).
When an employee performs such work without rubber insulating gloves, without insulating equipment covering energized parts, not using live‑line tools, and not performing live‑line barehand work under 1926.964(c), the employer must ensure the employee works from a position where they cannot reach into the employer's established minimum approach distance. See Requirements in 1926.960(d)(2).
When connecting to an energized circuit, the employee must first attach the conductor to the deenergized part; when disconnecting, the employee must remove the source end first; and employees must keep loose conductors away from exposed energized parts. See Making connections in 1926.960(e)(1)–(3).
Employees must remove or render nonconductive all exposed conductive articles (for example, keychains, watchbands, rings) when performing work within reaching distance of exposed energized parts, unless the employer determines those articles do not increase the hazard. See Conductive articles in 1926.960(f).
The employer must assess the workplace to identify employees exposed to hazards from flames or electric arcs, estimate the incident heat energy to which those employees would be exposed, and prohibit clothing that could melt onto skin or ignite (like untreated acetate, nylon, polyester, rayon, and polypropylene) unless treated to withstand the conditions or worn to eliminate the hazard. See Protection from flames and electric arcs in 1926.960(g). For guidance on performing PPE hazard assessments, see OSHA's interpretation on PPE hazard assessment responsibilities at https://www.osha.gov/laws-regs/standardinterpretations/2024-03-28.
Yes — the employer may make reasonable, broad estimates that cover multiple system areas provided the estimates use reasonable assumptions about energy‑exposure distribution and represent the maximum employee exposure for those areas; following Appendix E to the subpart is deemed compliance. See Estimate of available heat energy in 1926.960(g)(2).
Clothing made from acetate, nylon, polyester, rayon, and polypropylene (alone or in blends) is prohibited for employees exposed to flames or electric arcs unless the employer demonstrates the fabric has been treated to withstand the conditions or the clothing is worn in a manner that eliminates the hazard. See Prohibited clothing in 1926.960(g)(3).
The exception applies when work is performed with live‑line tools and the employee's position is such that they are neither within reach of nor otherwise exposed to contact with energized parts; in that case the two‑employee presence requirement does not apply. See Live‑line tools exception in 1926.960(b)(3)(ii)(B).
When work involves mechanical equipment (other than insulated aerial lifts) near parts energized above 600 volts, at least two employees shall be present while the work is performed, unless an applicable exception applies. See Mechanical equipment staffing requirement in 1926.960(b)(3)(i)(D).
Rubber insulating gloves together with rubber insulating sleeves constitute insulation from the energized part provided the employee has control of the part in a manner that prevents exposure of any uninsulated portions of the employee's body. See Glove and sleeve insulation condition in 1926.960(c)(1)(iii)(A).
Equipment must be considered energized unless it has been deenergized in accordance with [1926.961], so employers must follow 1926.961 procedures to take equipment out of the "treated as energized" status. See Treat as energized in 1926.960(b)(2).
When connecting deenergized equipment or lines to an energized circuit by means of a conducting wire or device, the employee must first attach the wire to the deenergized part, then to the energized circuit. See Connecting procedure in 1926.960(e)(1).
You must determine the minimum approach distance (MAD) using the formulas and tables in 1926.960(c)(1)(ii) or use the alternative tables in Appendix B if you follow the notes to those tables.
The employer’s obligation to make reasonable incident-energy estimates began on January 1, 2015, under 1926.960(g)(6)(i).
Under 1926.960(g)(4), the employer must ensure the outer layer of clothing is flame resistant when any of these apply: the worker may contact energized parts above 600 volts; an electric arc could ignite flammable material that could then ignite the worker’s clothing; molten metal or arcs from faulted conductors could ignite clothing (with a noted exception for conductors that can carry the available fault current without failure); or the estimated incident heat energy exceeds 2.0 cal/cm2.
Arc-rated protection for hands is not required when the employee is wearing rubber insulating gloves with protectors, or when the estimated incident energy is at most 14 cal/cm2 and the employee wears heavy-duty leather work gloves of at least 407 g/m2 (12 oz/yd2), per 1926.960(g)(5)(i).
Yes—under 1926.960(g)(5)(ii), arc-rated protection is not required for feet if the employee wears heavy-duty work shoes or boots.
Under 1926.960(g)(5)(iii)–(iv), head protection that meets 1926.100(b)(2) can be acceptable without arc-rated clothing for the head when the estimated incident energy is below 9 cal/cm2 for single-phase open-air arcs or below 5 cal/cm2 for other exposures; alternatively, a helmet plus a faceshield with at least an 8 cal/cm2 arc rating can be used where the estimated incident energy is less than 13 cal/cm2 for single-phase open-air arcs or less than 9 cal/cm2 for other exposures.
Under 1926.960(g)(5)(v), for single-phase arcs in open air the arc rating for an employee’s head and face protection may be up to 4 cal/cm2 less than the estimated incident energy.
The employer’s obligation to ensure employees exposed to electric arcs wear the required arc-rated protective equipment began on April 1, 2015, as stated in 1926.960(g)(6)(iii).
When installing or removing fuses with one or both terminals energized above 300 volts, you must use tools and gloves rated for the voltage and wear eye protection and be clear of the fuse exhaust path for expulsion-type fuses per 1926.960(h) and the expulsion-fuse requirement in the same section.
Yes—1926.960(i) says that the requirements for hazards from exposed live parts also apply when work is performed near covered (noninsulated) conductors.
Under 1926.960(j), non-current-carrying metal parts (like transformer cases or circuit-breaker housings) must be treated as energized at the highest voltage they may be exposed to unless the employer inspects and determines they are grounded before work begins.
For phase-to-phase voltages of 50 V to 300 V, the table instructs to 'Avoid contact,' meaning employees must avoid touching energized parts and maintain safe work practices to prevent contact, per the guidance in [1926.960] and its tables (Table V-5) in Appendix B (1926.960(c)(1)(ii)).
If employees will work above 900 meters (3,000 feet), you must multiply the distances in the tables (such as Table V-5) by the altitude correction factor from Table V-4 that corresponds to the worksite altitude, per [1926.960] and its notes in Appendix B ([1926.960] and Tables V-4/V-5).
Under 1926.960(g)(4)(iv), the outer layer must be flame resistant when the estimated incident heat energy exceeds 2.0 cal/cm2.
Before selecting arc-rated PPE, the employer must estimate the incident energy and then select PPE with arc ratings adequate to protect employees for the estimated energy exposure under 1926.960(g).
Under 1926.960(k)(1), any device used by employees to open circuits under load must be designed to interrupt the current involved.
If an employer uses the alternative MAD tables in Appendix B (Tables V-5 through V-8), the employer must follow the notes to those tables and ensure any site-specific corrections (like altitude or overvoltage factors) are applied as required; the standard does not prescribe a specific form of documentation, but employers should keep records showing they followed the table notes and applied required corrections.
The note to 1926.960(g)(4)(iii) clarifies that the molten metal or arcs provision does not apply to conductors that can carry the maximum available fault current without failing for the time it takes circuit protective devices to interrupt the fault.
Employers must assess hazards and make reasonable incident-energy estimates to select appropriate arc-rated clothing and equipment, and they should document the assessment as part of PPE selection; OSHA’s PPE hazard assessment guidance stresses that employers must assess the workplace to determine needed PPE before selection (OSHA LOI on PPE hazard assessment).
For expulsion-type fuses with one or both terminals energized above 300 volts, the employer must ensure the employee wears eye protection meeting subpart E, uses a tool rated for the voltage, and stands clear of the fuse barrel’s exhaust path, per the expulsion-fuse provision in 1926.960.
Employers may use the alternative minimum approach distances in Tables V-6 and V-7 (and other Appendix B tables) provided the worksite meets the conditions listed in the notes for those tables—most commonly that the worksite elevation is 900 meters (3,000 feet) or less unless you apply altitude correction—and, for some tables, that no insulated tool spans the gap and no large conductive object is in the gap, as explained in Appendix B and 1926.960(c)(1)(ii).
When an employee must install or remove fuses with exposed parts energized above 50 volts, the employer must ensure the employee uses tools or gloves rated for the voltage, per 1926.960(h).
The standard requires the outer layer of clothing to be flame resistant under the conditions in 1926.960(g)(4), except for clothing categories listed as not required to be arc-rated in 1926.960(g)(5)(i)–(v).
When calculating MAD for higher voltages under 1926.960(c)(1)(ii), the overvoltage (T) factor accounts for the maximum anticipated transient overvoltage and the altitude (A) factor corrects distances for reduced air density at higher elevations; both adjust the calculated MAD to reflect increased flashover risk.